COFRE DE PEROTE (TELCEL)

Project Date: October 3rd, 2005

1. Ohmic resistance:

Ground Resistivity Ground Resistivity Resistance of physical ground previously installed Resistance of Terragauss physical ground currently installed
Shelter
41.40 kOhms-m 505 Ohms 0.18 Ohms
Tower 1
11.07 kOhms-m 250 Ohms 0.16 Ohms
Tower 2
173.50 kOhms-m 2,130 Ohms 1.91 Ohms


2.- Voltage difference between neutral and ground inside the Shelter:

- Main board: 0.0 Volts.
- Contact: 0.0 Volts.

3.-Continuity measurement:

- Distance 1 m – it gets continuity
- Distance 30 m - it gets continuity.
- Distance 50 m - it gets continuity.

Caso de exito en Cofre de Perote

SITE CHOPCCA - CLARO PERU (AMERICA MOVIL)

Elaboration Project date: February 3rd, 2009

Ground type: Rocky.

Measurements of resistivity of the ground were taken in July, 2008 (dry season and low rain in the zone).

Resistivity measurements of the ground obtained are:

                         RESISTIVITY     Ohm-m                                    
Spacing (M) Reading 1 Reading 2 Resistivity Average (X)
1,00 21917,20 27757,60 24837,40
2,00 48481,60 61418,40 54950,00
3,00 80070,00 92692,80 86381,40
4,00 117561,60 133638,40 125600,00

Final resistance measurements of Terragauss Terragauss electromagnetic grounding system 4.85 and 4.51 Ohms, realized by ICA company.

TRIPLE PLAY LIMA - TELMEX (PHONE, TV & INTERNET)

Start Project Date: November, 2007

FIRST PHASE:
During this phase installation started around 2500 Terragauss electromagnetic grounding system, to land nodes and sources in all Lima city, Peru.

Caso de exito de Claro en Lima, Peru

CERRO DEL CHIQUIHUITE - MAXCOM

Project elaboration date: July 19th, 2004.

1.- Ohmic resistance:

Ground resistivity Resistance of physical ground previously installed (delta rods) Terragauss grounding system currently installed
Shelter
1160 Ohms-m   692 Ohms 1.47 Ohms

2.- Voltage difference between neutral and ground:

Voltage with previous physical grounding system (rods) Voltage with Terragauss physical grounding system
Shelter
60.7 Volts
0.014 Volts

3.-Continuity measurement:

Continuity with Previous physical grounding system (rods) Continuity with Terragauss physical grounding system
It didn’t get continuity It gets continuity

ITESM - CAMPUS SANTA FE

Project elaboration date: September 10th, 2004.

1.- Ohmic resistance:

Ground resistivity Resistance of physical ground previously installed (delta rods) Terragauss grounding system currently installed
Shelter
1,900 Ohms-m 1,200 Ohms 0.30 Ohms

2.- Voltage difference between neutral and ground:

Voltage with previous physical grounding system (rods) Voltage with Terragauss physical grounding system
3.4 Volts 0.007 Volts

3.-Continuity measurement:

Continuity with Previous physical grounding system (rods) Continuity with Terragauss physical grounding system
It didn’t get continuity It gets continuity

PARRES' PLANT - ASPHALT PLANT IN D.F.

Project elaboration date: December 1st, 2003

Headquarters Lightning Rods

1.- Ohmic resistance:

Ground resistivity Resistance of physical ground previously installed (delta rods) Terragauss grounding system currently installed
Shelter
4,600 Ohms-m 125 Ohms
145 Ohms
0.7 Ohms
1.1 Ohms

2.- Continuity measurement:

Continuity with Previous physical grounding system (rods) Continuity with Terragauss physical grounding system
It didn’t get continuity It gets continuity

Whole Substation 8

1.- Ohmic resistance:

Ground resistivity Resistance of physical ground previously installed (delta rods) Terragauss grounding system currently installed
Shelter
1,250 Ohms-m 1,200 Ohms 0.82 Ohms

2.- Voltage difference between neutral and ground::

Voltage with previous physical grounding system (rods) Voltage with Terragauss physical grounding system
2.5 Volts 0.007 Volts

3.-Continuity measurement:

Continuity with Previous physical grounding system (rods) Continuity with Terragauss physical grounding system
It didn’t get continuity It gets continuity

AEROPUESTOS Y SERVICIOS AUXILIARES (ASA) SITIO PRINCIPAL AEROPUERTO INTERNACIONAL CIUDAD DE MÉXICO

Project Elaboration Date: September 10th, 2004

We were selcter to participate in Reheabilitation wire proyect, electrical circuit and grounding to cover 20 airports and 40 fuel station in all over the country, certifying the contractors that will handle of the installation of our products.

Caso de exito en aeropuerto

RED VIRTUAL IMSS

Project Elaboration Date: January 13th, 2003

We have a participation with the Terragauss electromagnetic grounding system, for the Telecomunications Integral Network (IMSS private virtual network) to a National level, in Telmex Project..

Installation of the Terragauss electromagnetic grounding system in 3,000 places, 500 cities and 31 Mexico States.

Technical Training to 200 contractors to National Level, to elaborate this project.